High Temperature Single core cables with Reinforced Insulation 3.6/6 kV
CONSTRUCTIONConductorExtra flexible tinned annealed copper wires (red copper only for 150 C core temperature) class 6 according to HD 383InsulationSilicon rubber according to EN 50382-1 (EI 112)ELECTRICAL & MECHANICAL PROPERTIESNominal Voltage3.6/…
EN 50382-2 High Temperature Single Core Cables with Reinforced Insulation.pdf Contact us

CONSTRUCTION

ConductorExtra flexible tinned annealed copper wires (red copper only for 150 °C core temperature) class 6 according to HD 383
InsulationSilicon rubber according to EN 50382-1 (EI 112)

ELECTRICAL & MECHANICAL PROPERTIES

Nominal Voltage3.6/6 kV
Max. Conductor Temperature120°C /150°C (fixed installation)
Min. Permissible Ambient Temperature-25°C/-40°C (fixed installation)
Bending Radius

3 x Overall Diameter (D<12mm);

4 x Overall Diameter (D>12mm)

CHEMICAL & ENVIRONMENTAL PROPERTIE

EN 60684-2No fluorine
EN 50305; EN 60811-2-1Resistance to mineral oil & fuel oil, acid & alkali
EN 50305Resistance to ozone

FIRE PERFORMANCE FOR ROLLING STOCK APPLICATION

EN 50306-2Hazard levels HL1, HL2, HL3
DIN 5510-2Protection level 1/2/3/4
BS 6853Interior use 1a, 1b, II; Exterior use 1a, 1b, II
NF F 16-101F0
EN54454-2R15 Interior/ R16 Exterior HL1, HL2, HL3

FIRE PERFORMANCE IN GENERAL

EN 50265-2-1; IEC 60332-1-2; NF C 32-070 2.1 (C2)Vertical flame propogation for a single insulated wire or cable
EN 50266-2-4 + EN 50305; IEC 60332-3-24; NF C 32-070 2.2 (C1); VDE 0472 Teil 804Vertical flame spread of vertically mounted bunched wires or cables
EN 50268-2; IEC 61034-2; NF C 32-073 ;  NF C 20-902; NF F 16 101; VDE 0472 Teil 816Low Smoke Emission
EN 50267-2-1; IEC 60754-1; NF C 32-074;  NF C 20-454; VDE 0472 Teil 815Halogen Free
EN 50267-2-2/3; IEC 60754-2; NF C 32-074; NF C 20-453; VDE 0472 Teil 813Low Corrosivity (Acidity & Conductivity)
EN 50305; NF X 70-100; NF F 63 808; TM1-04; BS6853 Low Toxicity
NF F 63 808; BS6853; NF F 16 101Smoke index
EN45545-2Requirement for fire behavior of materials & components R15/R16

BRAIL HT-6SURI 3.6/6 KV

Nominal Cross- Sectional AreaConductor Diameter (a)Min. Mean Thickness of InsulationOverall DiameterWeightMax.Conductor ResistanceMin. Insulation Resistance
Tinned ConductorPlain Conductor
Min.Max.20°C20°C20°C150°C
mm²mmmmmmmmkg/kmΩ/kmΩ/kmMΩ x kmMΩ x km
509.23.015.217.85600.3930.3863400.70
7011.03.016.919.87700.2770.2723000.60
9512.53.018.321.49700.2100.2062700.55
12014.23.120.123.512000.1640.1612500.50
15015.83.121.625.314800.1320.1292200.45
18517.53.223.427.418000.1080.1062100.40

(a)= For information, indicative only