This 300/500V single core power cable is manufactured in accordance with BS 7211 and identified as BS Code 6241B. It features a cross-linked polyethylene (XLPE) insulated core and a low smoke zero halogen (LSZH) sheath, offering excellent thermal stability, fire performance, and electrical reliability. Widely used in power stations, underground passenger systems, airports, hotels, hospitals, high-rise buildings, and petrochemical facilities, it is ideal for applications where flame retardancy and low toxicity are essential. The cable is suitable for fixed wiring in dry or damp environments, especially where people safety and environmental protection are a concern..
Basic design to BS 7211:2012
Flame Retardance (Single vertical wire or cable test) | IEC 60332-1-2; EN 60332-1-2 |
Reduced Fire Propagation (Vertically-mounted bundled wires & cables test) | IEC 60332-3-24; EN 60332-3-24 |
Halogen Free | IEC 60754-1; EN 50267-2-1 |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2 |
Minimum Smoke Emission | IEC 61034-2; EN 61034-2 |
300/500V
Conductor : Annealed copper conductor, solid or stranded according to BS EN 60228 class 1 or class 2.
Insulation : XLPE type GP8 according to BS 7655-1.3. Crosslinked polyolefin material type EI 5 according to EN 50363-5 can be offered as option.
CPC (Circuit Protective Conductor) : Uninsulated copper conductor.
Outer Sheath : Extruded LSZH type LTS 2 according to BS 7655-6.1.
Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.
Insulation Colour :
Twin : Brown and blue or, for 2x1.0 and 2x1.5 cables, brown and brown.
Three cores : Brown, black (centre core) and grey.
Position of CPC :
Twin : Centrally placed between cores in same plane.
Three cores : Centrally placed between black and grey cores in same plane.
Sheath Colour : White; other colours can be offered upon request.
Maximum temperature range during operation : 90°C
Maximum short circuit temperature (5 Seconds) : 250°C
Minimum bending radius :
OD<8mm : 4 × Overall Diameter
8mm≤OD≤12mm : 5 × Overall Diameter
OD>12mm : 6 × Overall Diameter
Conductor | FLP300-RZ1-U/R | |||||||
---|---|---|---|---|---|---|---|---|
No. of Cores × Cross-sectional Area | Conductor Class | Nominal Insulation Thickness | Cross-sectional Area of CPC | Class of CPC | Nominal Sheath Thickness | Min. overall Dimensions | Max. overall Dimensions | Approx. Weight |
No.×mm² | mm | mm² | mm | mm | mm | kg/km | ||
2×1.0 | 1 | 0.7 | 1.0 | 1 | 0.9 | 4.1×7.6 | 5.0×9.2 | 68 |
2×1.5 | 1 | 0.7 | 1.0 | 1 | 0.9 | 4.4×8.1 | 5.3×9.7 | 85 |
2×2.5 | 1 | 0.7 | 1.5 | 1 | 1.0 | 4.9×9.3 | 6.0×11.2 | 120 |
3×1.0 | 1 | 0.7 | 1.0 | 1 | 0.9 | 4.1×10.0 | 5.0×12.1 | 91 |
3×1.5 | 1 | 0.7 | 1.0 | 1 | 0.9 | 4.4×10.7 | 5.3×12.9 | 115 |
3×2.5 | 1 | 0.7 | 1.5 | 1 | 1.0 | 4.9×12.0 | 6.0×14.6 | 170 |
2×1.0 | 2 | 0.7 | 1.0 | 1 | 0.9 | 4.2×7.8 | 5.1×9.4 | 73 |
2×1.5 | 2 | 0.7 | 1.0 | 1 | 0.9 | 4.5×8.3 | 5.4×10.0 | 90 |
2×2.5 | 2 | 0.7 | 1.5 | 1 | 1.0 | 5.0×9.5 | 6.1×11.4 | 125 |
2×4 | 2 | 0.7 | 1.5 | 1 | 1.0 | 5.5×10.4 | 6.7×12.6 | 175 |
2×6 | 2 | 0.7 | 2.5 | 1 | 1.1 | 6.2×12.0 | 7.5×14.6 | 240 |
2×10 | 2 | 0.7 | 4.0 | 2 | 1.2 | 7.3×14.5 | 8.8×17.5 | 390 |
2×16 | 2 | 0.7 | 6.0 | 2 | 1.3 | 8.4×17.0 | 10.1×20.5 | 560 |
3×4 | 2 | 0.7 | 1.5 | 1 | 1.0 | 5.5×14.0 | 6.7×16.9 | 196 |
3×6 | 2 | 0.7 | 2.5 | 1 | 1.1 | 6.2×16.2 | 7.5×19.5 | 291 |
3×10 | 2 | 0.7 | 4.0 | 2 | 1.2 | 7.3×19.5 | 8.8×23.6 | 440 |
3×16 | 2 | 0.7 | 6.0 | 2 | 1.3 | 8.4×22.8 | 10.1×27.6 | 670 |
Conductor operating temperature : 90°C
Ambient temperature : 30°C
Conductor Cross-sectional area | Ref. Method A (enclosed in conduit in thermally insulating wall etc.) | Ref. Method B (enclosed in conduit on a wall or in trunking etc.) | Ref. Method C (clipped direct) | Ref. Method E (free air or on a perforated cable tray etc. horizontal or vertical) | ||||
---|---|---|---|---|---|---|---|---|
1 two-core cable*, single-phase a.c. or d.c. | 1 three-or four core cable*, three- phase a.c. | 1 two-core cable*, single- phase a.c. or d.c. | 1 three-or four core cable*, three-phase a.c. | 1 two-core cable*, single-phase a.c. or d.c. | 1 three-or four core cable*, three- phase a.c. | 1 two-core cable*, single- phase a.c. or d.c. | 1 three-or four core cable*, three- phase a.c. | |
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
mm² | A | A | A | A | A | A | A | A |
1.0 | 14.5 | 13 | 17 | 15 | 19 | 17 | 21 | 18 |
1.5 | 18.5 | 16.5 | 22 | 19.5 | 24 | 22 | 26 | 23 |
2.5 | 25 | 22 | 30 | 26 | 33 | 30 | 36 | 32 |
4 | 33 | 30 | 40 | 35 | 45 | 40 | 49 | 42 |
6 | 42 | 38 | 51 | 44 | 58 | 52 | 63 | 54 |
10 | 57 | 51 | 69 | 60 | 80 | 71 | 86 | 75 |
16 | 76 | 68 | 91 | 80 | 107 | 96 | 115 | 100 |
Note: With or without a protective conductor.
Conductor cross-sectional area | Two-core cable, d.c. | Two-core cable, single-phase a.c. | Three or four core cable, three-phase a.c. |
---|---|---|---|
1 | 2 | 3 | 4 |
mm² | mV/A/m | mV/A/m | mV/A/m |
1.0 | 46 | 46 | 40 |
1.5 | 31 | 31 | 27 |
2.5 | 19 | 19 | 16 |
4 | 12 | 12 | 10 |
6 | 7.9 | 7.9 | 6.8 |
10 | 4.7 | 4.7 | 4.0 |
16 | 2.9 | 2.9 | 2.5 |