300/500V XLPE Insulated, LSZH Sheathed Power Cables to BS 7211 (2-3 Cores)
APPLICATIONThe cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.STANDARDSBasic design to BS 7211:2012FIRE PERFORMANCEFlame Retardance (Singl…
300_500V XLPE Insulated, LSZH Sheathed Power Cables to BS 7211 (2-3 Cores).pdf Contact us

APPLICATION

This 300/500V single core power cable is manufactured in accordance with BS 7211 and identified as BS Code 6241B. It features a cross-linked polyethylene (XLPE) insulated core and a low smoke zero halogen (LSZH) sheath, offering excellent thermal stability, fire performance, and electrical reliability. Widely used in power stations, underground passenger systems, airports, hotels, hospitals, high-rise buildings, and petrochemical facilities, it is ideal for applications where flame retardancy and low toxicity are essential. The cable is suitable for fixed wiring in dry or damp environments, especially where people safety and environmental protection are a concern..

STANDARDS

Basic design to BS 7211:2012

FIRE PERFORMANCE

Flame Retardance (Single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced Fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen FreeIEC 60754-1; EN 50267-2-1
No Corrosive Gas EmissionIEC 60754-2; EN 50267-2-2
Minimum Smoke EmissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

Conductor : Annealed copper conductor, solid or stranded according to BS EN 60228 class 1 or class 2.

Insulation : XLPE type GP8 according to BS 7655-1.3. Crosslinked polyolefin material type EI 5 according to EN 50363-5 can be offered as option.

CPC (Circuit Protective Conductor) : Uninsulated copper conductor.

Outer Sheath : Extruded LSZH type LTS 2 according to BS 7655-6.1.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Insulation Colour :

Twin : Brown and blue or, for 2x1.0 and 2x1.5 cables, brown and brown.

Three cores : Brown, black (centre core) and grey.

Position of CPC :

Twin : Centrally placed between cores in same plane.

Three cores : Centrally placed between black and grey cores in same plane.

Sheath Colour : White; other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius :

OD<8mm : 4 × Overall Diameter

8mm≤OD≤12mm : 5 × Overall Diameter

OD>12mm : 6 × Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFLP300-RZ1-U/R
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessCross-sectional Area of CPCClass of CPCNominal Sheath ThicknessMin. overall DimensionsMax. overall DimensionsApprox. Weight
No.×mm² mmmm² mmmmmmkg/km
2×1.010.71.010.94.1×7.65.0×9.268
2×1.510.71.010.94.4×8.15.3×9.785
2×2.510.71.511.04.9×9.36.0×11.2120
3×1.010.71.010.94.1×10.05.0×12.191
3×1.510.71.010.94.4×10.75.3×12.9115
3×2.510.71.511.04.9×12.06.0×14.6170
2×1.020.71.010.94.2×7.85.1×9.473
2×1.520.71.010.94.5×8.35.4×10.090
2×2.520.71.511.05.0×9.56.1×11.4125
2×420.71.511.05.5×10.46.7×12.6175
2×620.72.511.16.2×12.07.5×14.6240
2×1020.74.021.27.3×14.58.8×17.5390
2×1620.76.021.38.4×17.010.1×20.5560
3×420.71.511.05.5×14.06.7×16.9196
3×620.72.511.16.2×16.27.5×19.5291
3×1020.74.021.27.3×19.58.8×23.6440
3×1620.76.021.38.4×22.810.1×27.6670

ELECTRICAL PROPERTIES

Conductor operating temperature : 90°C

Ambient temperature : 30°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4E2A

Conductor Cross-sectional areaRef. Method A (enclosed in conduit in thermally insulating wall etc.)Ref. Method B (enclosed in conduit on a wall or in trunking etc.)Ref. Method C (clipped direct)Ref. Method E (free air or on a perforated cable tray etc. horizontal or vertical)
1 two-core cable*, single-phase a.c. or d.c.1 three-or four core cable*, three- phase a.c.1 two-core cable*, single- phase a.c. or d.c.1 three-or four core cable*, three-phase a.c.1 two-core cable*, single-phase a.c. or d.c.1 three-or four core cable*, three- phase a.c.1 two-core cable*, single- phase a.c. or d.c.1 three-or four core cable*, three- phase a.c.
123456789
mm²AAAAAAAA
1.014.513171519172118
1.518.516.52219.524222623
2.52522302633303632
43330403545404942
64238514458526354
105751696080718675
167668918010796115100

Note: With or without a protective conductor.

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E2B

Conductor cross-sectional areaTwo-core cable, d.c.Two-core cable, single-phase a.c.Three or four core cable, three-phase a.c.
1234
mm²mV/A/mmV/A/mmV/A/m
1.0464640
1.5313127
2.5191916
4121210
67.97.96.8
104.74.74.0
162.92.92.5