This high-quality LSZH (Low Smoke Zero Halogen) insulated cable complies with BS EN 50525-3-41 and is classified under BS code 2491B and hAR codes H05Z-U / H05Z-K. Rated for 300/500V, it is designed for fixed wiring in public and commercial buildings where fire safety and low smoke emissions are critical — including power stations, metro systems, airports, hotels, hospitals, petrochemical plants, and high-rise buildings. The non-sheathed structure allows for easy installation in conduits or trunking, while the LSZH insulation ensures superior flame retardancy, low toxicity, and safe evacuation conditions in case of fire.
Basic design to BS EN 50525-3-41(formerly BS 7211)
Flame Retardance (Single vertical wire or cable test) | IEC 60332-1-2; EN 60332-1-2 |
Halogen Free | IEC 60754-1; EN 50267-2-1 |
No Corrosive Gas Emission | IEC 60754-2; EN 50267-2-2 |
Minimum Smoke Emission | IEC 61034-2; EN 61034-2 |
300/500V
Conductor : Copper conductor according to BS EN 60228 class 1/2/5.
Insulation : Crosslinked polyolefin material type EI 5 according to EN 50363-5.
Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.
Black, Blue, Brown, Grey, Orange, Pink, Red, Turquoise, Violet, White, Green and Yellow. Bi-colours of any combination of the above mono-colours are permitted.
Maximum temperature range during operation : 90°C
Maximum short circuit temperature (5 Seconds) : 250°C
Minimum bending radius : 4 x Overall Diameter
Conductor | FLP300-Z-U/K | ||||
---|---|---|---|---|---|
No. of Cores × Cross-sectional Area | Conductor Class | Nominal Insulation Thickness | Min. Overall Diameter | Max. Overall Diameter | Approx. Weight |
No.×mm² | mm | mm | mm | kg/km | |
1×0.50 | 1 | 0.6 | 1.9 | 2.4 | 9.4 |
1×0.75 | 1 | 0.6 | 2.1 | 2.6 | 12.2 |
1×1.0 | 1 | 0.6 | 2.2 | 2.8 | 15.4 |
1×0.50 | 5 | 0.6 | 2.1 | 2.6 | 9.9 |
1×0.75 | 5 | 0.6 | 2.2 | 2.8 | 13.3 |
1×1.0 | 5 | 0.6 | 2.4 | 2.9 | 16.2 |
Conductor operating temperature : 90°C
Ambient temperature : 30°C
Conductor cross-sectional area | Single-phase a.c. | Three-phase a.c. |
---|---|---|
mm² | A | A |
0.5 | 3 | 3 |
0.75 | 6 | 6 |
1.0 | 10 | 10 |
Note: These values apply to the majority of cases. Further information should be sought in unusual cases eg.: (i) When high ambient temperatures are involved, ie. above 30°C (ii) Where long lengths are used (iii) Where ventilation is restricted (iv) Where the cords are used for other purposes, ego internal wiring of apparatus. |
Conductor cross-sectional area | 2 cables d.c. | 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||
---|---|---|---|---|---|---|---|---|
Ref. Methods A&B (enclosed in conduit or trunking) | Ref. Methods C, F&G (clipped direct, on trays or in free air) | Ref. Methods A&B (enclosed in conduit or trunking) | Ref. Methods C, F&G (clipped direct, on trays or in free air) | |||||
Cables touching | Cables spaced* | Cables touching, Trefoil | Cables touching, flat | Cables spaced*, flat | ||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 |
mm² | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m | mV/A/m |
0.5 | 101 | 101 | 101 | 101 | 87 | 87 | 87 | 87 |
0.75 | 68 | 68 | 68 | 68 | 59 | 59 | 59 | 59 |
1.0 | 50 | 50 | 50 | 50 | 44 | 44 | 44 | 44 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.