SHD-GC 2kV Mining Heavy-Duty PowerCable: Engineered for DemandingIndustrial Environments
The SHD-GC series is a heavy-duty, three-core, round portable power cable rated at 2kV, specifically designed for the extreme conditions encountered in mining and heavy industrial applications . Its robust CPE jacket delivers exceptional resistance to abrasion, tear, and chemicals , ensuring reliable performance under harsh operating conditions .
ICEA S-75-381/NEMA WC 58
ASTM B 172
ASTM B 33
CAN/CSA C22.2 No. 96
| Conductors | Stranded annealed tinned copper conductor. | 
|---|---|
| Insulation | Ethylene Propylene Rubber (EPR). | 
| Insulation Shield | Tinned copper/textile braid. | 
| Ground Check Conductor | Tinned copper conductor with a yellow polypropylene insulation. | 
| Grounding Conductor | Tinned copper conductor. | 
| Jacket | Reinforced extra-heavy-duty Chlorinated Polyethylene (CPE), black. | 
Other jacket materials such as CSP/PCP/NBR/PVC are available upon request.
Two-layer jacket with reinforcing fibre between the two layers can be offered as an option.
| Minimum Bending Radius | 6×OD | 
|---|---|
| Maximum Conductor Operating Temperature | +90℃ | 
| Construction | No. of Strands | Grounding Conductor Size | Ground Check Conductor Size | Nominal Insulation Thickness | Nominal Jacket Thickness | Nominal Overall Diameter Height×Width | Nominal Weight | Ampacity | ||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| No. of cores × AWG/kcmil | - | AWG/kcmil | AWG/kcmil | inch | mm | inch | mm | inch | mm | lbs/kft | kg/km | A | 
| 3×6 | 133 | 10 | 10 | 0.07 | 1.8 | 0.155 | 3.9 | 1.29 | 32.8 | 1130 | 1682 | 93 | 
| 3×4 | 259 | 8 | 10 | 0.07 | 1.8 | 0.155 | 3.9 | 1.40 | 35.6 | 1460 | 2173 | 122 | 
| 3×3 | 259 | 7 | 10 | 0.07 | 1.8 | 0.170 | 4.3 | 1.51 | 38.3 | 1680 | 2500 | 140 | 
| 3×2 | 259 | 6 | 10 | 0.07 | 1.8 | 0.170 | 4.3 | 1.59 | 40.4 | 1990 | 2961 | 159 | 
| 3×1 | 259 | 5 | 8 | 0.08 | 2.0 | 0.190 | 4.8 | 1.76 | 44.7 | 2385 | 3549 | 184 | 
| 3×1/0 | 266 | 4 | 8 | 0.08 | 2.0 | 0.190 | 4.8 | 1.86 | 47.2 | 2765 | 4115 | 211 | 
| 3×2/0 | 329 | 3 | 8 | 0.08 | 2.0 | 0.205 | 5.2 | 2.00 | 50.8 | 3255 | 4844 | 243 | 
| 3×3/0 | 418 | 2 | 8 | 0.08 | 2.0 | 0.205 | 5.2 | 2.13 | 54.1 | 3890 | 5789 | 279 | 
| 3×4/0 | 532 | 1 | 8 | 0.08 | 2.0 | 0.220 | 5.6 | 2.31 | 58.7 | 4720 | 7024 | 321 | 
| 3×250 | 627 | 1/0 | 6 | 0.095 | 2.4 | 0.220 | 5.6 | 2.51 | 63.8 | 5460 | 8125 | 355 | 
| 3×300 | 741 | 1/0 | 6 | 0.095 | 2.4 | 0.235 | 6.0 | 2.68 | 68.1 | 6395 | 9517 | 398 | 
| 3×350 | 888 | 2/0 | 6 | 0.095 | 2.4 | 0.235 | 6.0 | 2.81 | 71.4 | 7280 | 10834 | 435 | 
| 3×500 | 1221 | 4/0 | 6 | 0.095 | 2.4 | 0.265 | 6.7 | 3.19 | 81.0 | 9820 | 14614 | 536 | 
Ampacity-Based on a conductor temperature of 90℃ and an ambient air temperature of 40℃, per ICEA S-75-381.
                
            