XLPE Insulated, PVC Sheathed 2 core+E Armored Cables, 0.6/1kV
APPLICATIONThese cables are used for mains, submains and subcircuits unenclosed, enclosed in conduit, buried direct or in underground ducts for buildings and industrial plants where not subject to mechanical damage.STANDARDAS/NZS 5000.1AS/NZS 3008AS/N…
XLPE Insulated, PVC Sheathed 2 core+E ArmoredCables, 0.6_1kV.pdf Contact us

APPLICATION

These cables are used for mains, submains and subcircuits unenclosed, enclosed in conduit, buried direct or in underground ducts for buildings and industrial plants where not subject to mechanical damage.

STANDARD

  • AS/NZS 5000.1

  • AS/NZS 3008

  • AS/NZS 1125

CONSTRUCTION

ConductorPlain annealed copper.
InsulationXLPE X-90.
Insulation colour:2C + E - Red, Black, Green/yellow
Bedding:Polyvinylchloride compound PVC 5V-90
Bedding colour:Black
Armour:Galvanised Steel Wire
Sheath:Polyvinylchloride compound PVC 5V-90
Sheath colour:Orange, other colors are available upon request

TECHNICAL CHARACTERISTICS

ConductorCurrent RatingsElectrical Characteristics
Nominal Area
mm^2
Unenclosed In Air
A
Buried Direct ABuried In Ducts
A
Maximum DC Resistance @20°C
Ohm/km
Maximum AC Resistance @90°C
Ohm/km
Reactance
Ohm/km
Single Phase Voltage Drop @90°C
mV/Am
16971301001.151.470.08052.95
251301701300.7270.9270.08081.86
351602051600.5240.6690.07861.35
501952451900.3870.4940.07511.00
702503002350.2680.3430.07410.703
953103602850.1930.2480.07250.520
1203604103250.1530.1970.07130.423

CABLE PARAMETER

Nom. conductor area
mm^2
Conductor No./ ODNom. insulation thickness mmNom. earth conductor area
mm^2
Nom. earth
conductor insulation thickness mm
Nom. diameter over bedding mmArmour diameter mmNom. overall diameter mmApprox. mass kg/km
167/1.700.760.715.31.2521.61100
257/2.140.960.719.21.2525.81310
357/2.650.9100.721.31.626.81765
5019/1.891.0160.724.11.629.72185
7019/2.241.1250.928.21.633.62745
9519/2.651.1250.931.72.037.73650
12019/2.941.2350.935.42.041.84600