French Standard H05V2-U / H07V2-U
APPLICATION AND DESCRIPTIONThese cables are for fixed protected installation inside appliances and in, or on, lighting fittings. Suitable for installation in surface mounted or embedded conduits, only for signalling and control circuits. Maximum condu…
H05V2-U H07V2-U .pdf Contact us

APPLICATION AND DESCRIPTION

These cables are for fixed protected installation inside appliances and in, or on, lighting fittings. Suitable for installation in surface mounted or embedded conduits, only for signalling and control circuits. Maximum conductor temperature in normal use 90°C. Not to be used in contact with object higher then 85°C. Not suitable for fixed distribution system.

STANDARD AND APPROVAL

  • CEI20-20/7, HD 21.7 S2, CE Low Voltage Directive 73/23/EEC and 93/68/EEC, ROHS compliant

CABLE CONSTRUCTION

Technical Characteristics

Solid bare copper single wire
Solid to DIN VDE 0281-3,NF C 32-201-3 and IEC 60227-3
Special PVC TI3 ore insulation
Cores to VDE-0293 colors on chart
H05V-U (20, 18 & 17 AWG)
H07V-U (16 AWG and Larger)

 

Working voltage300/500v (H05V-U)
Working voltage450/750v (H07V-U)
Test voltage2000V(H05V-U)/2500V (H07V-U)
Flexing bending radius15 x O
Static bending radius15 x O
Flexing temperature-5oC to +70oC
Static temperature-30oC to +80oC
Short circuit temperature+160oC
Flame retardantIEC 60332.1
Insulation resistance10 MΩ x km

CABLE PARAMETER

AWGNo. of Cores x Nominal Cross Sectional AreaNominal Thickness of InsulationNominal Overall DiameterNominal Copper WeightNominal Weight

# x mm^2mmmmkg/kmkg/km
201 x 0.50.62.14.89
181 x 0.750.62.27.211
171 x 10.62.49.614
161 x 1.50.72.914.421
141 x 2.50.83.524.033
121 x 40.83.938.049
101 x 60.84.558.069
81 x 101.05.796.0