French Standard H05BN4-F
APPLICATION AND DESCRIPTIONThese EPR (ethylen-propylen rubber) insulated and CSP (chlorosulphonated polyethylene rubber or similar) sheathed electric cables can be used either in dry, humid or wet places or in contact with oil or grease, in weather co…
H05BN4-F .pdf Contact us

APPLICATION AND DESCRIPTION

These EPR (ethylen-propylen rubber) insulated and CSP (chlorosulphonated polyethylene rubber or similar) sheathed electric cables can be used either in dry, humid or wet places or in contact with oil or grease, in weather conditions and under weak mechanical stress, for example for power supply to small appliances in industrial plants, machine shops, heating plates, portable lamps, farming equipment etc.

They are also suitable for caravans and camping equipment... The maximum conductor temperature in normal use: 90°C. While high temperature use, skin contact must be avoided.

STANDARD AND APPROVAL

  • CEI 20-19/12, CEI 20-35 (EN 60332-1), BS6500, BS7919,

  • ROHS compliant, VDE 0282 Part-12, IEC 60245-4, CE Low-Voltage

CABLE CONSTRUCTION

Technical Characteristics

Fine bare copper strands
Strands to VDE-0295 Class-5, IEC 60228 Class-5
EPR(Ethylene Propylene Rubber) rubber EI7 insulation
Color code VDE-0293-308
CSP(Chlorosulphonated Polyethylene) outer jacket EM7

 

Working voltage300/500 volts
Test voltage2000 volts
Flexing bending radius6.0 x O
Fixed bending radius4.0 x O
Temperature Range-20oC to +90oC
Maximum Short Circuit Temperature+250oC
Flame retardantIEC 60332.1
Insulation resistance20 MΩ x km

CABLE PARAMETER

AWGNo. of Cores x Nominal Cross Sectional AreaNominal Thickness of InsulationNominal Thickness of SheathNominal Overall DiameterNominal Copper WeightNominal Weight

# x mm^2mmmmmmkg/kmkg/km
18(24/32)2 x 0.750.60.86.12954
18(24/32)3 x 0.750.60.96.74368
18(24/32)4 x 0.750.60.97.35882
18(24/32)5 x 0.750.61.08.172108
17(32/32)2 x 10.60.96.61965
17(32/32)3 x 10.60.97.02978
17(32/32)4 x 10.60.97.63895
17(32/32)5 x 10.61.08.551125