This high-performance BS 6231 600/1000V PVC insulated,non-sheathed flexible cable is designed for 600/1000V applications and manufactured according to BS TYPE BK / TYPE CK standards. It is mainly used for the internal wiring of switchboards, control panels, metering units, relay cabinets, and instrument panels of power switchgear. It is also suitable for internal connections within rectifier systems, motor starters, and controllers. Constructed with stranded copper conductors and high-grade PVC insulation, the cable offers mechanical flexibility, flame retardance, and excellent electrical performance in compact control and automation environments.
Basic design to to BS 6231: 2006
Flame Retardance (Single Vertical Wire Test) | BS EN 60332-1-2 |
600/1000V
Conductor : Annealed copper conductor, class 5 according to BS EN 60228.
Insulation : PVC Type TI 1 according to BS EN 50363-3 for cable type BK, and type TI 3 according to BS EN 50363-3 for cable type CK.
Black, Blue, Brown, Red, White, Grey, Violet, Pink, Green and Yellow. Other colours can be offered upon request.
Maximum temperature range during operation (PVC) : 70°C (TYPE BK) ; 90°C (TYPE CK)
Maximum short circuit temperature (5 Seconds) : 160°C
Minimum bending radius : 6 × overall diameter
Conductor | FLP600-V-K | |||
---|---|---|---|---|
No. of Cores ×Cross Section | Class of Conductor | Nominal Insulation Thickness | Maximum Overall Diameter | Approx.Weight |
No.× mm² | mm | mm | kg/km | |
1x0.50 | 5 | 0.8 | 3 | 12 |
1x0.75 | 5 | 0.8 | 3.1 | 15 |
1x1.0 | 5 | 0.8 | 3.3 | 18 |
1x1.5 | 5 | 0.8 | 3.6 | 23 |
1x2.5 | 5 | 0.8 | 4.1 | 34 |
1x4.0 | 5 | 0.8 | 4.8 | 48 |
1x6.0 | 5 | 0.8 | 5.3 | 67 |
1x10 | 5 | 1 | 7.2 | 119 |
1x16 | 5 | 1 | 9 | 187 |
1x25 | 5 | 1.2 | 11.5 | 291 |
1x35 | 5 | 1.2 | 12.5 | 406 |
1x50 | 5 | 1.4 | 15.4 | 580 |
1x70 | 5 | 1.4 | 17.5 | 780 |
1x95 | 5 | 1.6 | 19.2 | 1055 |
1x120 | 5 | 1.6 | 21.2 | 1175 |
1x150 | 5 | 1.8 | 23.9 | 1425 |
1x185 | 5 | 2 | 25.9 | 1735 |
1x240 | 5 | 2.2 | 28.9 | 2310 |
Conductor Operating Temperature : 70°C
Ambient Temperature : 30°C
Conductor cross-sectional area | Reference Method A (enclosed in conduit in thermally insulating wall etc) | Reference Method B (enclosed in conduit on a wall or in trunking etc) | Reference Method C (clipped direct) | Reference Method F (in free air or on a perforated cable tray horizontal or vertical etc) | |||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Touching | Spaced by one cable diameter | ||||||||||
2 cables, single-phase a.c. or d.c. | 3 or 4cables, three-phase a.c. | 2 cables, single-phase a.c. or d.c | 3 or 4 cables, three-phase a.c. | 2 cables, single-phase a.c. or d.c. flat and touching | 3 or 4 cables, three-phase a.c. flat and touching or trefoil | 2 cables, single-phase a.c. or d.c. flat | 3 cables, three-phase a.c. flat | 3 cables, three-phase a.c. trefoil | 2 cables, single-phase a.c. or d.c. or 3 cables three-phase a.c. flat | ||
Horizontal | Vertical | ||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 |
mm² | A | A | A | A | A | A | A | A | A | A | A |
1 | 11 | 10.5 | 13.5 | 12 | 15.5 | 14 | - | - | - | - | - |
1.5 | 14.5 | 13.5 | 17.5 | 15.5 | 20 | 18 | - | - | - | - | - |
2.5 | 20 | 18 | 24 | 21 | 27 | 25 | - | - | - | - | - |
4 | 26 | 24 | 32 | 28 | 37 | 33 | - | - | - | - | - |
6 | 34 | 31 | 41 | 36 | 47 | 43 | - | - | - | - | - |
10 | 46 | 42 | 57 | 50 | 65 | 59 | - | - | - | - | - |
16 | 61 | 56 | 76 | 68 | 87 | 79 | - | - | - | - | - |
25 | 80 | 73 | 101 | 89 | 114 | 104 | 131 | 114 | 110 | 146 | 130 |
35 | 99 | 89 | 125 | 110 | 141 | 129 | 162 | 143 | 137 | 181 | 162 |
50 | 119 | 108 | 151 | 134 | 182 | 167 | 196 | 174 | 167 | 219 | 197 |
70 | 151 | 136 | 192 | 171 | 234 | 214 | 251 | 225 | 216 | 281 | 254 |
95 | 182 | 164 | 232 | 207 | 284 | 261 | 304 | 275 | 264 | 341 | 311 |
120 | 210 | 188 | 269 | 239 | 330 | 303 | 352 | 321 | 308 | 396 | 362 |
150 | 240 | 216 | 300 | 262 | 381 | 349 | 406 | 372 | 356 | 456 | 419 |
185 | 273 | 245 | 341 | 296 | 436 | 400 | 463 | 427 | 409 | 521 | 480 |
240 | 321 | 286 | 400 | 346 | 515 | 472 | 546 | 507 | 485 | 615 | 569 |
Nominal Cross Section Area | 2 cables d.c.
| 2 cables, single-phase a.c. | 3 or 4 cables, three-phase a.c. | |||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Ref. Methods A and B (enclosed in conduit or trunking) | Ref. Methods C & F (clipped direct, on trays or in free air) | Ref. Methods A & B (enclosed in conduit or trunking) | Ref. Methods C & F (clipped direct, on trays or in free air) | |||||||||||||||||||
Cables touching | Cables spaced* | Cables touching, Trefoil | Cables touching, Flat | Cables spaced*, Flat | ||||||||||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | ||||||||||||||
mm² | mV/A/m | |||||||||||||||||||||
1 | 44 | 44 | 44 | 44 | 38 | 38 | 38 | 38 | ||||||||||||||
1.5 | 29 | 29 | 29 | 29 | 25 | 25 | 25 | 25 | ||||||||||||||
2.5 | 18 | 18 | 18 | 18 | 15 | 15 | 15 | 15 | ||||||||||||||
4 | 11 | 11 | 11 | 11 | 9.5 | 9.5 | 9.5 | 9.5 | ||||||||||||||
6 | 7.3 | 7.3 | 7.3 | 7.3 | 6.4 | 6.4 | 6.4 | 6.4 | ||||||||||||||
10 | 4.4 | 4.4 | 4.4 | 4.4 | 3.8 | 3.8 | 3.8 | 3.8 | ||||||||||||||
16 | 2.8 | 2.8 | 2.8 | 2.8 | 2.4 | 2.4 | 2.4 | 2.4 | ||||||||||||||
r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | r | x | z | ||
25 | 1.75 | 1.8 | 0.33 | 1.8 | 1.75 | 0.2 | 1.75 | 1.75 | 0.29 | 1.8 | 1.5 | 0.29 | 1.55 | 1.5 | 0.175 | 1.5 | 1.5 | 0.25 | 1.55 | 1.5 | 0.32 | 1.55 |
35 | 1.25 | 1.3 | 0.31 | 1.3 | 1.25 | 0.195 | 1.25 | 1.25 | 0.28 | 1.3 | 1.1 | 0.27 | 1.1 | 1.1 | 0.17 | 1.1 | 1.1 | 0.24 | 1.1 | 1.1 | 0.32 | 1.15 |
50 | 0.93 | 0.95 | 0.3 | 1 | 0.93 | 0.19 | 0.95 | 0.93 | 0.28 | 0.97 | 0.81 | 0.26 | 0.85 | 0.8 | 0.165 | 0.82 | 0.8 | 0.24 | 0.84 | 0.8 | 0.32 | 0.86 |
70 | 0.63 | 0.65 | 0.29 | 0.72 | 0.63 | 0.185 | 0.66 | 0.63 | 0.27 | 0.69 | 0.56 | 0.25 | 0.61 | 0.55 | 0.16 | 0.57 | 0.55 | 0.24 | 0.6 | 0.55 | 0.31 | 0.63 |
95 | 0.46 | 0.49 | 0.28 | 0.56 | 0.47 | 0.18 | 0.5 | 0.47 | 0.27 | 0.54 | 0.42 | 0.24 | 0.48 | 0.41 | 0.155 | 0.43 | 0.41 | 0.23 | 0.47 | 0.4 | 0.31 | 0.51 |
120 | 0.36 | 0.39 | 0.27 | 0.47 | 0.37 | 0.175 | 0.41 | 0.37 | 0.26 | 0.45 | 0.33 | 0.23 | 0.41 | 0.32 | 0.15 | 0.36 | 0.32 | 0.23 | 0.4 | 0.32 | 0.3 | 0.44 |
150 | 0.29 | 0.31 | 0.27 | 0.41 | 0.3 | 0.175 | 0.34 | 0.29 | 0.26 | 0.39 | 0.27 | 0.23 | 0.36 | 0.26 | 0.15 | 0.3 | 0.26 | 0.23 | 0.34 | 0.26 | 0.3 | 0.4 |
185 | 0.23 | 0.25 | 0.27 | 0.37 | 0.24 | 0.17 | 0.29 | 0.24 | 0.26 | 0.35 | 0.22 | 0.23 | 0.32 | 0.21 | 0.145 | 0.26 | 0.21 | 0.22 | 0.31 | 0.21 | 0.3 | 0.36 |
240 | 0.18 | 0.195 | 0.26 | 0.33 | 0.185 | 0.165 | 0.25 | 0.185 | 0.25 | 0.31 | 0.17 | 0.23 | 0.29 | 0.16 | 0.145 | 0.22 | 0.16 | 0.22 | 0.27 | 0.16 | 0.29 | 0.34 |
Note: *Spacings larger than one cable diameter will result in a large voltage drop.
r = conductor resistance at operating temperature
x = reactance
z = impedance