Point Heating Cables to NR/SP/ELP/40045
APPLICATIONPoint Heating Cables to NR/SP/ELP/40045 are designed for power distribution in points heating system. These heavy duty cables offer protection from abrasion and mechanical impact whilst maintaining fl exibility to ease installation.STANDARD…
Point Heating Cablesto NR_SP_ELP_40045.pdf Contact us

APPLICATION

Point Heating Cables to NR/SP/ELP/40045 are designed for power distribution in points heating system. These heavy duty cables offer protection from abrasion and mechanical impact whilst maintaining fl exibility to ease installation.

STANDARD

  • NR/SP/ELP/40045 (formerly RT/E/PS/40045)

  • BS 7919

  • UNE 21027

CABLE CONSTRUCTION

  • Electrical Characteristics at 20℃Conductors: Class 5 tinned copper conductors to BS 6360.

  • Insulation: EPR type GP4 to BS 7655.

  • Sheath: PCP type EM2 to BS 7655.

Nominal Conductor Cross Sectionmm^21.52.54.06.0
Maximum DC Conductor ResistanceΩ/km13.78.215.093.39
Voltage RatingKV0.3/0.5

MECHANICAL AND THERMAL PROPERTIES

  • Minimum Bending Radius: 7.5×OD

  • Temperature Range: -30℃ to +70℃ (during operation); -10℃ +55℃ (during installation)

CORE IDENTIFICATION

  • 4cores: yellow, yellow, blue, blue

  • 8cores: yellow, yellow, blue, blue, Brown, brown, black, black

DIMENSIONS AND WEIGHT

Cable CodeNo. of cores& Nominal
Conductor Cross
Sectional Area
No.×mm^2
No. & Nominal
Diameter of
Strands
No/mm
Nominal
Thickness of
Insulation
mm
Nominal
Overall
Diameter
mm
Nominal
Weight
kg/km
BRF40045-H05RNF-300/500V-4G1.54×1.530/0.250.814.3220
BRF40045-H05RNF-300/500V-4G2.54×2.550/0.250.916.5390
BRF40045-H05RNF-300/500V-4G44×4.056/0.301.018.5420
BRF40045-H05RNF-300/500V-8G1.58×1.530/0.250.818.5460
BRF40045-H05RNF-300/500V-8G2.58×2.550/0.250.921.4510
BRF40045-H05RNF-300/500V-8G48×4.056/0.251.023.6830
BRF40045-H05RNF-300/500V-8G68×6.084/0.301.025.61040
BRF40045-H05RNF-300/500V-8G108×10.075/0.401.231.71799
BRF40045-H05RNF-300/500V-8G168×16.0118/0.401.236.22480