600/1000V Mica+XLPE Insulated, LSZH Sheathed, Armoured Power Cables to IEC 60502-1 (Single Core)
APPLICATIONThe cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.STANDARDSBasic design adapted from IEC 60502-1FIRE PERFORMANCECircuit Integr…
600_1000V Mica+XLPE Insulated, LSZH Sheathed,Armoured Power Cables to IEC 60502-1 (Single Core).pdf Contact us

APPLICATION

The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.

STANDARDS

Basic design adapted from IEC 60502-1

FIRE PERFORMANCE

Circuit IntegrityIEC 60331-21; EN 6387; BS 8491
Flame Retardance (Single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen FreeIEC 60754-1; EN 50267-2-1
No Corrosive Gas emissionIEC 60754-2; EN 50267-2-2
Minimum smoke emissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

Conductor : The conductors shall be class 2 plain or metal-coated annealed copper in accordance with IEC 60228. Class 1 and class 5 conductor can be offered as option.

Fire Barrier : Mica glass tape.

Insulation : Thermosetting XLPE material and thickness shall be as per IEC 60502-1.

Inner Covering Option : Thermoplastic halogen free compound ST8 as per IEC 60502-1.

Armouring : Aluminium wire.

Outer Sheath : Thermoplastic halogen free compound ST8 as per IEC 60502-1.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Insulation Colour : Brown or blue; other colours can be offered upon request.

Sheath Colour : Black; other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius : 6 × Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFRP600-mRZ1MAZ1-R
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessNominal Inner Covering ThicknessNominal AL Wire DiameterNominal Sheath ThicknessApprox. Overall DiameterApprox. Weight
no.×mm² mmmmmmmmmmkg/km
1×420.71.00.81.812.2205
1×620.71.00.81.812.7238
1×1020.71.00.81.813.7300
1×1620.71.00.81.814.7383
1×2520.91.00.81.816.4520
1×3520.91.01.251.818.5695
1×5021.01.01.251.820.0864
1×7021.11.01.251.822.01132
1×9521.11.01.61.825.01530
1×12021.21.01.61.826.81840
1×15021.41.01.61.828.82186
1×18521.61.01.61.831.42680
1×24021.71.01.61.934.53380
1×30021.81.02.02.038.54255
1×40022.01.22.02.242.35298
1×50022.21.22.02.346.46551

ELECTRICAL PROPERTIES

Conductor operating temperature : 90°C

Ambient temperature : 30°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4E3A

Conductor cross- sectional areaRef. Method c (clipped direct)Ref. Method f (in free air or on a perforated cable tray, horizontal or vertical)
TouchingTouchingSpaced by on cable diameter
2 cables, single-phase a.c. or d.c. flat3 or 4 cables, three-phase a.c. flat2 cables, single- phase a.c. or d.c. flat3 or 4 cables, three-phase a.c. flat3 cables three-phase a.c. trefoil2 cables, d.c.2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
HorizontalVerticalHorizontalVerticalHorizontalVertical
123456789101112
mm²AAAAAAAAAAA
50237220253232222284270282266288266
70303277322293285356349357337358331
95367333389352346446426436412425393
120425383449405402519497504477485449
150488437516462463600575566539549510
185557496587524529688660643614618574
240656579689612625815782749714715666
300755662792700720943906842805810755
40085371789976781511371094929889848797
5009627911016851918131412661032989923871

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4E3B

Conductor cross-sectional area2 cables d.c.2 cables, single-phase a.c.3 or 4 cables, three-phase a.c.
TouchingSpaced*Trefoil and touchingFlat and touchingFlat and spaced*
1234567
mm²mV/A/mmV/A/mmV/A/mmV/A/mmV/A/mmV/A/m
  rxzrxzrxzrxzrxz
500.980.990.211.000.980.291.000.860.1800.870.840.250.880.840.330.90
700.670.680.200.710.690.290.750.590.1700.620.600.250.650.620.320.70
950.490.510.1950.550.530.280.600.440.1700.470.460.240.520.490.310.58
1200.390.410.1900.450.430.270.510.350.1650.390.380.340.440.410.300.51
1500.310.330.1850.380.360.270.450.290.1600.330.310.230.390.340.390.45
1850.250.270.1850.330.300.260.400.230.1600.280.260.230.340.290.290.41
2400.1950.210.1800.280.240.260.350.1800.1550.240.210.220.300.240.280.37
3000.1550.170.1750.250.1950.250.320.1450.1500.210.1700.220.280.200.270.34
4000.1150.1450.1700.220.1800.240.300.1250.1500.1950.1600.210.270.200.270.33
5000.0930.1250.1700.210.1650.240.290.1050.1450.1800.1450.200.250.1900.240.31

Note: *Spacings larger than one cable diameter will result in a large voltage drop.

r = conductor resistance at operating temperature

x = reactance

z = impedance