600/1000V Mica+XLPE Insulated, LSZH Sheathed, Armoured Cables to BS 7846 (2-5 Cores & Multicore)
APPLICATIONThe cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.STANDARDSBasic design to BS 7846FIRE PERFORMANCECircuit IntegrityIEC 60331-2…
600_1000V Mica+XLPE Insulated, LSZH Sheathed,Armoured Power Cables to BS 7846 (2-5 Cores & Multicore).pdf Contact us
no moreno more

APPLICATION

The cables are mainly used in power stations, mass transit underground passenger systems, airports, petrochemical plants, hotels, hospitals and high-rise buildings.

STANDARDS

Basic design to BS 7846

FIRE PERFORMANCE

Circuit IntegrityIEC 60331-21; EN 6387; BS 8491
Flame Retardance (single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen FreeIEC 60754-1; EN 50267-2-1
No Corrosive Gas emissionIEC 60754-2; EN 50267-2-2
Minimum smoke emissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

600/1000V

CABLE CONSTRUCTION

Conductor : Annealed copper wire, stranded according to BS EN 60228 class 2.

Fire Barrier : Mica glass tape.

Insulation : XLPE type GP 8 according to BS 7655-1.3. HEPR type GP 6 according to BS 7655-1.2 or crosslinked polyolefin material type EI 5 according to BS EN 50363-5 can be offered as option.

Bedding : Extruded layer of polymeric material.

Armouring : Galvanized steel wire.

Outer Sheath : Extruded layer of polymeric material LTS 1 according to BS 7655-6.1.

Outer Sheath Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Insulation Colour

2-core : Brown and blue.

3-core : Brown, black and grey.

4-core : Blue, brown, black and grey.

5-core : Green-and-yellow, blue, brown, black, grey.

Sheath Colour : Black; other colours can be offered upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 90°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius : 8 x Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFRP600-mRZ1MZ1-R
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessNominal Bedding ThicknessNominal Steel Wire Armour DiameterNominal Sheath ThicknessApprox. Overall DiameterApprox. Weight
No.×mm² mmmmmmmmmmkg/km
2 cores
2×1.5a20.60.80.91.313.5345
2×2.5a20.70.80.91.414.9413
2×4a20.70.80.91.416.0478
2×4a&c20.70.81.251.416.7581
2×6a20.70.80.91.417.2555
2×6a&c20.70.81.251.417.9666
2×10a20.70.80.91.519.2708
2×10a&c20.70.81.251.519.9832
2×16a20.70.81.251.522.01036
2×25a20.90.81.251.625.71386
2×25b20.90.81.251.623.51311
2×35a20.91.01.61.729.01918
2×35b20.91.01.61.726.51814
2×50b21.01.01.61.828.52330
2×70b21.11.01.61.932.02968
2×95b21.11.22.02.036.04085
2×120b21.21.22.02.139.04846
2×150b21.41.22.02.242.06223
2×185b21.61.42.52.448.07479
2×240b21.71.42.52.552.09137
2×300b21.81.62.52.657.010937
2×400b22.01.62.52.862.013316
3 cores
3×1.5a20.60.80.91.314.1384
3×2.5a20.70.80.91.415.6467
3×4a20.70.80.91.416.8551
3×4a&c20.70.81.251.417.5659
3×6a20.70.80.91.418.0652
3×6a&c20.70.81.251.418.7768
3×10a20.70.81.251.520.9985
3×16a20.70.81.251.623.41269
3×25a20.91.01.61.728.41953
3×25b20.91.01.61.726.51874
3×35a20.91.01.61.831.02393
3×35b20.91.01.61.828.52286
3×50b21.01.01.61.832.02952
3×70b21.11.01.61.935.03852
3×95b21.11.22.02.140.05312
3×120b21.21.22.02.244.06364
3×150b21.41.42.52.349.08113
3×185b21.61.42.52.453.09706
3×240b21.71.42.52.658.012045
3×300b21.81.62.52.763.014536
3×400b22.01.62.52.970.017866
4 cores
4×1.5a20.60.80.91.315.1433
4×2.5a20.70.80.91.416.7532
4×4a20.70.80.91.418.1637
4×4a&c20.70.81.251.418.8856
4×6a20.70.81.251.520.3901
4×10a20.70.81.251.522.61159
4×16a20.70.81.251.625.31516
4×25a20.91.01.61.730.82341
4×25b20.91.01.61.729.52286
4×35a20.91.01.61.833.72898
4×35b20.91.01.61.832.02824
4×50b21.01.01.61.935.03628
4×70b21.11.22.02.141.05188
4×95b21.11.22.02.245.06585
4×120b21.21.42.52.350.08520
4×150b21.41.42.52.455.010071
4×185b21.61.42.52.660.012149
4×240b21.71.62.52.766.015217
4×300b21.81.62.52.970.018373
4×400b22.01.83.153.281.023960
5 cores
5×1.520.60.80.91.416.3495
5×2.520.70.80.91.418.0603
5×420.70.80.91.519.7739
5×4b20.70.81.251.520.4869
5×620.70.81.251.521.91031
5×1020.70.81.251.624.61356
5×1620.71.01.61.728.72010
5×2520.91.01.61.833.62762
5×3520.91.01.61.936.93440
5×5021.01.22.02.042.44700
5×7021.11.22.02.248.26186
Multicore
7×1.520.60.80.91.417.5574
7×1.5c20.60.81.251.418.2687
7×2.520.70.80.91.419.3711
7×2.5c20.70.81.251.420.0837
7×420.70.81.251.521.81024
12×1.520.60.81.251.622.7968
12×2.520.70.81.251.625.51218
12×420.70.81.251.528.81725
19×1.520.61.01.61.626.11255
19×2.520.70.81.61.730.51844
19×420.71.01.61.733.22285
27×1.520.61.01.61.731.71856
27×2.520.61.01.61.735.72367
27×420.71.01.61.939.22993
37×1.520.71.01.61.734.92223
37×2.520.71.01.61.739.42878
37×420.71.22.02.044.84109

a Circular or compacted circular stranded conductor (Class 2).

b Shaped stranded conductor (Class 2).

c Cables with alternative armour wire size.