300/500V Mica+SR Insulated, LSZH Sheathed, Screened Power Cables to BS 7629-1 (2-4 Cores & Multcore)
APPLICATIONThe cables are primarily intended for use in the following applications:BS 5266-1 for emergency lighting of premises.BS 5839-1 for fire detection and fire alarm systems in and around building.BS 5839-8 for voice alarm systems.BS 5839-9 for …
300_500V SR Insulated, LSZH Sheathed,Screened Power Cables to BS 7629-1 (2-4 Cores & Multcore).pdf Contact us

APPLICATION

The cables are primarily intended for use in the following applications:

BS 5266-1 for emergency lighting of premises.

BS 5839-1 for fire detection and fire alarm systems in and around building.

BS 5839-8 for voice alarm systems.

BS 5839-9 for emergency voice communication systems.

STANDARDS

Basic design to BS 7629-1:2015

FIRE PERFORMANCE

Circuit IntegrityBS 6387; BS EN50200; BS 8434-2
Flame Retardance (Single vertical wire or cable test)IEC 60332-1-2; EN 60332-1-2
Reduced Fire Propagation (Vertically-mounted bundled wires & cables test)IEC 60332-3-24; EN 60332-3-24
Halogen FreeIEC 60754-1; EN 50267-2-1
No Corrosive Gas emissionIEC 60754-2; EN 50267-2-2
Minimum Smoke emissionIEC 61034-2; EN 61034-2

VOLTAGE RATING

300/500V

CABLE CONSTRUCTION

Conductor : Copper conductor according to BS EN 60228 class 1/2.

Fire Barrier : Mica glass tape.

Insulation : Fire resistant special ceramized silicone rubber compound type EI 2 as per BS EN 50363-1.

Screened : One or more metallic or laminated metallic tape(s) shall be applied, either longitudinally or helically or a combination of both, with the metallic element in contact with the uninsulated circuit protective conductor or drain wire.

Circuit Protective Conductor : Uninsulated tinned copper conductor of the same section and class as the insulated conductors in the two,three and four cores cables.

Sheath : Extruded LSZH type LTS 3 according to BS 7655-6.1.

Insulation Option : UV resistance, hydrocarbon resistance, oil resistance, anti-rodent and anti-termite properties can be offered as option.

COLOUR CODE

Insulation Colour :

Number of coresCore colours or numbering
2 cores+uninsulated circuit protective conductorBrown, Blue or Brown, Brown
3 cores+uninsulated circuit protective conductorBrown, Black, Grey
4 cores+uninsulated circuit protective conductorBrown, Blue, Black, Grey
7, 12 and19 cores+uninsulated drain wireNumbers 1, 2, 3, 4, 5, 6, 7 and upwards or, for identification by colour, an identical colour(excluding brown and black),except for two adjacent cores in each layer distinctively coloured brown and black.

Sheath Colour : Colours upon request.

PHYSICAL AND THERMAL PROPERTIES

Maximum temperature range during operation : 70°C

Maximum short circuit temperature (5 Seconds) : 250°C

Minimum bending radius : 6 x Overall Diameter

CONSTRUCTION PARAMETERS

ConductorFRP300-mSOZ1-U/R PH120
No. of Cores × Cross-sectional AreaConductor ClassNominal Insulation ThicknessCPC Nominal Cross-sectional AreaNominal Sheath ThicknessApprox. Overall DiameterApprox. Weight
no.×mm² mmmm²mmmmkg/km
2 cores
2x1.01/20.61.00.910.0103
2x1.51/20.71.50.910.5130
2x2.51/20.82.51.012.5181
2x4.01/20.84.01.114.5246
3 cores
3x1.51/20.71.50.911.7166
3x2.51/20.82.51.013.7232
3x4.01/20.84.01.115.7318
4 cores
4x1.51/20.71.51.012.9211
4x2.51/20.82.51.114.4294
4x4.01/20.84.01.217.4403
7 cores
7x1.51/20.70.51.115.5331
7x2.51/20.80.51.218.0698
12 cores
12x1.51/20.70.51.220.2537
12x2.51/20.80.51.424.21093
19 cores
19x1.51/20.70.51.324.0802

ELECTRICAL PROPERTIES

Conductor operating temperature : 70°C

Ambient temperature : 30°C

Current-Carrying Capacities (Amp) according to BS 7671:2008 table 4D2A

Conductor cross-sectional areaRef. Method A (enclosed in conduit in thermally insulating wall etc)Ref. Method B (enclosed in conduit on a wall or in trunking etc)Ref. Method C (clipped direct)Ref. Method E (in free air or on a perforated cable tray etc. horizontal or vertical)
1 two-core cable*, single-phase a.c. or d.c.1 three-core or 1 four-core cable*, three-phase a.c.1 two-core cable*, singlephase a.c. or d.c.1 three-core or 1 four-core cable*, three-phase a.c.1 two-core cable*, single-phase a.c. or d.c.1 three-core or 1 four-core cable*, three-phase a.c.1 two-core cable*, single-phase a.c. or d.c.1 three-core or 1 four-core cable*, three-phase a.c.
123456789
mm²AAAAAAAA
1.011101311.51513.51714.5
1.5141316.51519.517.52218.5
2.518.517.5232027243025
42523302736324034

Note: *With or without a protective conductor.

Voltage Drop (Per Amp Per Meter) according to BS 7671:2008 table 4D2B

Conductor cross-sectional areaTwo-core cable d.c.Two-core cable single-phase a.c.Three- or four-core cable, three-phase a.c.
1234
mm²mV/A/mmV/A/mmV/A/m
1.0444438
1.5292925
2.5181815
411119.5