PVC Insulated, 3 Core + E Flat Cables, 450/750V
APPLICATIONThese cables are used for general wiring, unenclosed, enclosed in conduit, buried direct or in underground ducts for domestic, commercial and industrial installations where not subject to mechanical damage. Suitable for balanced three phase…
PVC Insulated, 3 Core + E Flat Cables, 450_750V.pdf Contact us

APPLICATION

These cables are used for general wiring, unenclosed, enclosed in conduit, buried direct or in underground ducts for domestic, commercial and industrial installations where not subject to mechanical damage. Suitable for balanced three phase applications with E.

STANDARD

  • AS/NZS 5000.2

  • AS 1125

  • AS 3808

CONSTRUCTION

ConductorPlain annealed copper
Maximum operating temperature: 90°C
InsulationPVC V90
Insulation colour:Red, Black, Green/yellow
Sheath:Polyvinylchloride compound PVC 3V90
Sheath colour:White, other colors are available upon request

TECHNICAL CHARACTERISTICS

ConductorCurrent RatingsElectrical Characteristics
Nominal Area
mm^2
Unenclosed In Air
A
Surrounded by thermal insulation
A
Buried In Ducts
A
Maximum DC Resistance @20°C
Ohm/km
Maximum AC Resistance @75°C
Ohm/km
Reactance
Ohm/km
Three Phase Voltage Drop
mV/Am
11471718.127.00.11946.8
1.51792113.617.30.11130.0
2.52513297.419.450.10216.4
43317374.615.880.10210.2
64222473.083.930.09676.8
105829631.832.330.09064.05
167839811.151.470.08612.55

CABLE PARAMETER

Nom. conductor area
mm^2
Conductor
No./ OD
Nom. insulation thickness
mm
earth conductor area
mm^2
Nom. sheath thickness
mm
Nom. overall diameter
mm
Approx. mass
kg/km
MinMax
1.01/1.130.61.00.911.1x4.111.8x4.495
1.57/0.500.61.50.912.6x4.513.3x4.8120
2.57/0.670.72.5115.6x5.416.4x5.7190
47/0.850.82.51.117.7x6.218.6x6.7290
67/1.041.02.51.119.5x6.920.4x7.3370
107/1.351.041.224.0x8.224.5x8.7540
167/1.701.061.327.8x9.529.1x10.0820