PVC Insulated, PVC Sheathed 2 core+E Unarmored Cables, 0.6/1kV
APPLICATIONThese cables are used for mains, submains and subcircuits unenclosed, enclosed in conduit, buried direct or in underground ducts for buildings and industrial plants where not subject to mechanical damage.STANDARDAS/NZS 5000.1AS/NZS 3008AS/N…
PVC Insulated, PVC Sheathed 2 core+E UnarmoredCables, 0.6_1kV.pdf Contact us

APPLICATION

These cables are used for mains, submains and subcircuits unenclosed, enclosed in conduit, buried direct or in underground ducts for buildings and industrial plants where not subject to mechanical damage.

STANDARD

  • AS/NZS 5000.1

  • AS/NZS 3008

  • AS/NZS 1125

CONSTRUCTION

ConductorPlain annealed copper.
InsulationPolyvinylchloride compound PVC V-90
Insulation colour:2C + E - Red, Black, Green/yellow
Sheath:Polyvinylchloride compound PVC 5V-90
Sheath colour:Black, other colors are available upon request

TECHNICAL CHARACTERISTICS

ConductorCurrent RatingsElectrical Characteristics
Nominal Area
mm^2
Unenclosed In Air
A
Buried Direct
A
Buried In Ducts
A
Maximum DC Resistance @20°C
Ohm/km
Maximum AC Resistance @75°C
Ohm/km
Reactance
Ohm/km
Single Phase Voltage Drop @75°C
mV/Am
1.518142213.616.50.11133.0
2.52620317.419.010.10218.0
43426404.615.610.10211.2
64434513.083.750.09677.50
106047681.832.230.09064.46
168063881.151.400.08612.81
25105881150.7270.8840.08531.78
351301051400.5240.6380.08261.28
501601251650.3870.4710.07970.957
702001552050.2680.3270.07700.673
952501902500.1930.2360.07660.498

CABLE PARAMETER

Nom. conductor area
mm^2
Conductor
No./ OD
Nom. insulation thickness
mm
Nom. earth conductor area
mm^2
Nom. earth conductor insulation thickness
mm
Nom. overall diameter
mm
Approx. mass
kg/km
1.57/0.500.81.50.610.6160
2.57/0.670.82.50.711.6220
47/0.851.02.50.713.1295
67/1.041.02.50.714.2335
107/1.351.041.015.9440
167/1.701.061.017.9620
257/2.141.261.021.6840
357/2.651.2101.022.81090
5019/1.891.4161.025.81465
7019/2.241.4251.230.41900
9519/2.651.6251.234.82500