NSGAFOU Cables
APPLICATIONThe cables are designed for use in switch cabinets, wiring of devices, trains and buses as well as in dry rooms.STANDARDDIN VDE 0250-602CABLE CONSTRUCTIONElectrical Characteristics at 20℃Conductors: Flexible tinned copper to IEC 60228 clas…
NSGAFOU Cables.pdf Contact us

APPLICATION

The cables are designed for use in switch cabinets, wiring of devices, trains and buses as well as in dry rooms.

STANDARD

  • DIN VDE 0250-602

CABLE CONSTRUCTION

  • Electrical Characteristics at 20℃Conductors: Flexible tinned copper to IEC 60228 class 5.

  • Insulation: EPR type 3G13.

  • Outer sheath: PCP type 5GM3.

Nominal Conductor Cross Sectionmm^21.52.54.06.010162535
Conductor ResistanceΩ/km13.78.215.093.391.951.240.7950.565
Current RatingA31415875103145194240
Voltage RatingKV1.8/3
Nominal Conductor Cross Sectionmm^2507095120150185240
Conductor ResistanceΩ/km0.3930.2770.210.1640.1320.1090.0817
Current RatingA301372456528607639821
Voltage RatingKV1.8/3

MECHANICAL AND THERMAL PROPERTIES

  • Minimum Bending Radius: 4×OD

  • Temperature Range: -25℃ to +80℃ (during operation); -10℃ to +60℃ (during installation)

DIMENSIONS AND WEIGHT

Cable CodeNo. of cores& Nominal
Conductor Cross
Sectional Area
No.×mm^2
No. & Nominal
Diameter of
Strands
No/mm
Nominal
Insulation
Thickness
mm
Nominal
Overall
Diameter
mm
Nominal
Weight
kg/km
BRF602-NSGAFOU-1G1.51×1.530/0.251.36.559
BRF602-NSGAFOU-1G2.51×2.550/0.251.36.874
BRF602-NSGAFOU-1G41×4.056/0.31.37.794
BRF602-NSGAFOU-1G61×6.084/0.31.38.3118
BRF602-NSGAFOU-1G101×10.080/0.41.59.2163
BRF602-NSGAFOU-1G161×16.0126/0.41.510.1220
BRF602-NSGAFOU-1G251×25.0196/0.401.812.5336
BRF602-NSGAFOU-1G351×35.0276/0.401.814.0470
BRF602-NSGAFOU-1G501×50.0396/0.401.815.5581
BRF602-NSGAFOU-1G701×70.0360/0.501.817.0772
BRF602-NSGAFOU-1G951×95.0475/0.502.219.51030
BRF602-NSGAFOU-1G1201×120.0608/0.502.221.21280
BRF602-NSGAFOU-1G1501×150.0756/0.502.223.51650
BRF602-NSGAFOU-1G1851×185.0925/0.502.425.62050
BRF602-NSGAFOU-1G2401×240.01221/0.502.627.32590