33KV Power Cables to BS 7835 NR/PS/ELP/00008
APPLICATIONThe cables are used to distribute three phase a.c. electrical power supplies at nominal system voltages of 33KV to traction substations on D.C. electrified lines.STANDARDNR/PS/ELP/00008(formerly RT/E/PS/00008)BS 6622, BS 6234, BS 7454IEC 60…
33KV Power Cablesto BS 7835 NR_PS_00008.pdf Contact us

APPLICATION

The cables are used to distribute three phase a.c. electrical power supplies at nominal system voltages of 33KV to traction substations on D.C. electrified lines.

STANDARD

  • NR/PS/ELP/00008(formerly RT/E/PS/00008)

  • BS 6622, BS 6234, BS 7454

  • IEC 60502-2, IEC60840

CABLE CONSTRUCTION

  • Electrical Characteristics at 20℃Conductors: Class 1 circular solid aluminium (for 185 mm^2) or class 2 compact circular stranded plain copper (for 300mm^2) to BS EN 60228: 2005 (previously BS 6360).

  • Conductor Screen: Extruded semi-conducting XLPE (Cross-Linked Polyethylene) solidly bonded.

  • Insulation: XLPE (Cross-Linked Polyethylene).

  • Insulation Screen: Extruded semi-conducting XLPE (Cross-Linked Polyethylene), solidly bonded and cold strippable.

  • Separator: Semi conducting water blocking tape.

  • Screen: Copper wire screen, helically wound with equalising copper tape.

  • Separator: Semi conducting water blocking tape.

  • Sheath: Graphite coated MDPE type TS2.

Nominal Conductor Cross Sectionmm^2185300
Maximum DC Conductor ResistanceΩ/km0.1640.0601
CapacitanceμF/km0.2050.243
Voltage RatingKV19/3319/33

MECHANICAL AND THERMAL PROPERTIES

  • Minimum Bending Radius: 15×OD

  • Temperature Range: 0℃ to +90℃ (during operation); 0℃ to +60℃ (during installation)

DIMENSIONS AND WEIGHT

Cable CodeNo. of cores&
Nominal Conductor
Cross Sectional Area
No.×mm^2
Nominal
Thickness of
Conductor Screen
mm
Nominal Thickness
of Insulation
&Insulation Screen
mm/mm
Nominal
Overall
Diameter
mm
Nominal
Weight
kg/km
BRF00008-RHZ1H16-19/33KV-1G185AL1×1850.98.0/0.645.02200
BRF00008-RHZ1H16-19/33KV-1G300CU1×3000.98.0/0.650.04500